Calculators · Voltage Drop Calculator

Electrical

Voltage Drop Calculator

Enter the voltage, current, length and copper wire size. Get the voltage drop in volts and percent.

DC and single-phase use two wires. Three-phase uses the line-to-line voltage.

For example 12, 120, 240 or 480.

Amps the circuit carries.

From the source to the load, not the round trip.

AWG or kcmil.

Stranded adds 2 percent to the resistance.

Resistance rises with heat. 75 °C is a cautious choice.

Used to find the smallest size that meets it.

How to use the voltage drop calculator

Choose the type of circuit and type the supply voltage, the load current and the one-way length. Pick the copper wire size and the conductor temperature. The calculator gives the drop in volts and in percent, the voltage left at the load, and the resistance it used. It also shows the smallest listed size that stays within your target drop, by voltage drop alone. Use the length from the source to the load, because the formula already counts the return path.

The voltage drop formula

Voltage drop is the current times the resistance of the wire. For a DC or single-phase circuit the current flows out and back, so the length counts twice. For a balanced three-phase circuit the factor is the square root of three. This is the form used in Southwire's voltage drop guide (checked October 2026), where the resistance comes from a material constant and the circular mils of the wire.

CircuitVoltage drop in voltsPercent drop
DC or single-phaseVD = 2 × I × R × L ÷ 1,000VD ÷ V × 100
Three-phase (balanced)VD = √3 × I × R × L ÷ 1,000VD ÷ V × 100

I is the current in amps, R is the resistance in ohms per 1,000 feet, and L is the one-way length in feet. V is the supply voltage, which for three-phase is the line-to-line voltage.

Where the resistance comes from

The calculator does not use a pasted table. It works the resistance out from the properties of copper published in the NBS Handbook 100, Copper Wire Tables (a U.S. government publication, checked October 2026). The Handbook gives annealed copper a resistivity of 10.371 ohm-circular mils per foot at 20 °C and a temperature coefficient of 0.00393 per °C. It lists the area of each AWG size in circular mils, and it says stranded conductors have a resistance 2 to 5 percent above the solid equivalent, with 2 percent adopted up to 2,000,000 circular mils. So:

  • Solid resistance at 20 °C = 10.371 × 1,000 ÷ circular mils, in ohms per 1,000 ft
  • Stranded = solid × 1.02
  • At temperature t = resistance at 20 °C × [1 + 0.00393 × (t − 20)]

Our results agree with the stranded-copper values in the Handbook's own table 17 (8 AWG and larger) to within about 0.5 percent, which is the rounding of the Handbook's three-digit values. Smaller stranded sizes use the same 2 percent rule. Here is what the calculator uses for stranded copper at 75 °C and at 25 °C.

SizeCircular milsΩ per 1,000 ft at 75 °CΩ per 1,000 ft at 25 °C
18 AWG1,6207.94136.6582
16 AWG2,5804.98644.1807
14 AWG4,1103.13022.6244
12 AWG6,5301.97011.6518
10 AWG10,3801.23941.0391
8 AWG16,5100.77920.6533
6 AWG26,2400.49030.4111
4 AWG41,7400.30820.2584
2 AWG66,3600.19390.1625
1/0 AWG105,6000.12180.1021
4/0 AWG211,6000.06080.0510
500 kcmil500,0000.02570.0216
1000 kcmil1,000,0000.01290.0108

Example: a 20 amp load 100 feet away on 120 volts

A 20 amp single-phase load sits 100 feet from the panel, on a 120 volt circuit. The wire is stranded copper at 75 °C. The table shows how the size changes the drop. The target is 3 percent, which is 3.6 volts.

SizeOperationDropPercentAt the load
14 AWG2 × 20 × 3.1302 × 100 ÷ 1,00012.52 V10.43 %107.48 V
12 AWG2 × 20 × 1.9701 × 100 ÷ 1,0007.88 V6.57 %112.12 V
10 AWG2 × 20 × 1.2394 × 100 ÷ 1,0004.96 V4.13 %115.04 V
8 AWG2 × 20 × 0.7792 × 100 ÷ 1,0003.12 V2.60 %116.88 V
6 AWG2 × 20 × 0.4903 × 100 ÷ 1,0001.96 V1.63 %118.04 V

Only 8 AWG and larger stay under 3 percent in this run, so the calculator names 8 AWG as the smallest size by voltage drop. That says nothing about whether the wire may be used for a 20 amp circuit. Ampacity and overcurrent protection are a separate check done under the electrical code.

A 20 amp load 100 feet from a 120 volt panel A single-phase circuit: the panel at 120 volts and a 20 amp load 100 feet away. The current goes out on one wire and back on the other, so it travels 200 feet. With 10 AWG copper the drop is 2 × 20 × 1.2394 × 100 ÷ 1,000 = 4.96 volts, or 4.13 percent. Panel 120 V Load 20 A out → ← back One-way length 100 ft (the current travels 2 × 100 ft) Drop = 2 × I × R × L ÷ 1,000 10 AWG: 2 × 20 × 1.2394 × 100 ÷ 1,000 = 4.96 V (4.13%)
The first worked example on this page. Lengths are not to scale.

Example: a three-phase feeder on 208 volts

A balanced three-phase load draws 100 amps at 208 volts line to line, 150 feet from the source. The wire is stranded copper at 75 °C. With 1/0 AWG the drop is √3 × 100 × 0.1218 × 150 ÷ 1,000 = 3.17 volts, or 1.52 percent. With 3 AWG it is 6.35 volts (3.05 percent), and with 3/0 AWG it is 1.99 volts (0.96 percent).

How to reduce voltage drop

The formula shows every lever you have. The drop is the current times the resistance times the length, and the resistance falls as the wire gets thicker. Southwire's guide lists the same factors: conductor length, load current, conductor size, conductor material, operating temperature, power factor and system voltage. We read it in October 2026. Here is what each change does to the run in the first example, 20 amps over 100 feet on 120 volts, which drops 7.88 volts (6.57 percent) on 12 AWG stranded copper at 75 °C.

ChangeWhat changes in the formulaDropPercent
None (12 AWG, 100 ft, 20 A, 120 V)2 × 20 × 1.9701 × 100 ÷ 1,0007.88 V6.57 %
Larger wire, 10 AWGR falls to 1.2394 Ω per 1,000 ft4.96 V4.13 %
Larger wire, 8 AWGR falls to 0.7792 Ω per 1,000 ft3.12 V2.60 %
Half the length, 50 ftL is halved3.94 V3.28 %
Half the current, 10 AI is halved3.94 V3.28 %
Same 2,400 W load on 240 VI = 2,400 ÷ 240 = 10 A, and V doubles3.94 V1.64 %
Cooler wire, 25 °CR falls to 1.6518 Ω per 1,000 ft6.61 V5.51 %
  • Use a larger wire. More circular mils means less resistance, so every step up the size list cuts the drop. The calculator names the smallest size that meets your target.
  • Shorten the run. The drop grows in step with the length. Southwire recommends measuring the route the cable really takes, not the straight-line distance, so measure it before you decide.
  • Lower the current. The drop grows in step with the current too. Southwire also recommends checking the drop at the maximum load you expect, so type the highest current the circuit will carry.
  • Use a higher voltage. For the same power, twice the voltage means half the current. The drop in volts halves, and as a share of a supply twice as large it falls to a quarter. This only works if the equipment is made for the higher voltage.
  • Copper or aluminum. Southwire notes that copper has lower resistance than aluminum. The NBS Handbook 109, Aluminum Wire Tables (1972, read in October 2026) lists four conductor grades of aluminum at 52.5 to 61.8 percent of the conductivity of the copper standard. For the same circular mils that is 1.6 to 1.9 times the resistance of copper, so an aluminum run needs a larger size to drop the same voltage. This calculator covers copper only. For aluminum cable, use the resistance in the maker’s data sheet with the same formula.
  • Keep the wire cool. Resistance rises with heat, so the same run drops more in a hot space than in a cool one. Southwire recommends correcting for temperature when conditions are hotter than the standard assumptions. Pick the conductor temperature that fits your installation.

Motors and other inductive loads add reactance, which this calculator does not model (see below). And a larger wire only changes the voltage drop. Whether a wire may carry the current is still a separate check under the electrical code.

What target drop should I use?

There is no single number. A 3 percent target is common and is the figure the U.S. Department of Energy cites in a motor systems tip sheet (checked October 2026). Southwire's guide shows 3 and 5 percent targets in the context of the Canadian code. Sensitive equipment, motors and low-voltage lighting often need less, because a few volts are a large share of a small supply voltage. Check your local code, the equipment data and the job specification.

What this calculator does not do

  • Ampacity. It does not tell you whether a wire can carry the current safely.
  • Reactance and skin effect. It uses DC resistance only. Southwire's guide notes that long runs, large conductors and motor loads call for an impedance method.
  • Aluminum. It covers copper only. See “Copper or aluminum” above and use the maker’s data for aluminum cable.
  • Flexible cords and fine-stranded cable. Their resistance is higher than the 2 percent used here. Use the maker's data.
  • Motor starting and voltage at the panel. It works from the supply voltage you type.

To turn watts into amps first, use the watts to amps calculator. For the relation between volts, amps and ohms, see the Ohm's law calculator.

Frequently asked questions

How do you calculate voltage drop?

Multiply the current by the resistance of the wire, and count the wire both ways. For a DC or single-phase circuit, the drop in volts is 2 × amps × ohms per 1,000 ft × length in feet ÷ 1,000, where the length is the one-way distance. For a balanced three-phase circuit, replace the 2 with √3 (1.732). Divide the drop by the supply voltage to get the percentage.

How much voltage drop is there in 100 feet?

It depends on the wire size and the current. For 20 amps over 100 feet one way on 12 AWG stranded copper at 75 °C, the drop is 7.88 volts. On a 120 volt circuit that is 6.57 percent. The same run in 8 AWG drops 3.12 volts (2.60 percent) and in 10 AWG 4.96 volts (4.13 percent).

What is the rule of thumb for voltage drop?

A common target is 3 percent. The U.S. Department of Energy cites a 3 percent limit in its motor systems tip sheet, and Southwire shows 3 and 5 percent targets in its voltage drop guide, which is written for the Canadian code. This calculator starts at 3 percent and lets you change it. Your local code, the equipment maker and the project specification decide what applies to your job.

What is the voltage drop on 18 gauge wire?

Stranded 18 AWG copper has about 6.66 ohms per 1,000 feet at 25 °C. Carrying 1 amp over 50 feet one way (100 feet of wire out and back), it drops 0.67 volts. On a 12 volt circuit that is 5.55 percent, which is why low-voltage runs need thicker wire than most people expect. Enter your own current and length above.

Does this calculator work for three-phase circuits?

Yes. Choose three-phase and type the line-to-line voltage, such as 208 or 480. The calculator uses the √3 factor and assumes the three phases are balanced. For a load wired line to neutral, use the single-phase setting with the line-to-neutral voltage.

Can I use it for aluminum wire?

No. The calculator covers copper only. Aluminum has more resistance than copper of the same size, so the same run drops more voltage. We did not find an open source for the resistance of today’s aluminum building cable that we could check, so we left it out instead of guessing. For aluminum, use the resistance in the conductor maker’s data sheet and the same formula.

Does the smallest size shown mean the wire is safe to use?

No. The smallest size is the first one whose voltage drop falls within your target, and nothing else. It does not check whether the wire can carry the current without overheating (ampacity), and it does not consider the breaker, the insulation or the installation conditions. Those depend on the National Electrical Code and your local rules, and a licensed electrician must confirm them.

How can I reduce voltage drop?

Use a larger wire, shorten the run, lower the current on the circuit or, if the equipment is made for it, run it at a higher voltage. Copper has lower resistance than aluminum of the same size. In the example of 20 amps over 100 feet on 120 volts, going from 12 AWG to 8 AWG stranded copper cuts the drop from 6.57 to 2.60 percent. A larger wire does not replace the ampacity check required by the electrical code.

Does a higher voltage reduce voltage drop?

For the same power, yes. Doubling the voltage halves the current, so the drop in volts halves and the percentage falls to a quarter. A 2,400 watt load that draws 20 amps at 120 volts and 10 amps at 240 volts, 100 feet away on 12 AWG stranded copper at 75 °C, drops 6.57 percent at 120 volts and 1.64 percent at 240 volts. The equipment must be rated for the higher voltage.

We use our own technical cookies and, if you allow it, Google Analytics cookies to see which calculators are used most. Press “Accept” to allow analytics, “Reject” to refuse them or “Configure” to choose. If you don’t accept, we still measure visits without cookies and with approximate figures. You can change your mind at any time from the footer. More details in the cookie policy.